Features
- Corona Discharge Sensor, proven technology
- Microprocessor controlled circuit with Advanced Digital Signal Processing, monitors the sensing tip up to 2000 times per second
- Detects all halogenated refrigerants, including A2L refrigerants
- Variable frequency audible alarm
- 14" Flexible stainless steel probe with Teflon™ liner
- Rubber cushion grip
- Constant power indication
- Power supply 3 V DC, two “C” cell alkaline batteries (included)
- Sensing tip life: approx. 20 hours (two tips included)
- Operating temp. -20° to 52° C
- Blow molded carrying case included, optional holster
- Certified to SAE J2913 / SAE J2791 / E-35422 / EN 14624
- UL Classified and CE approved
- 2 year warranty.
Specifications
Ultimate Sensitivity |
< < 3 g/year (0.1 oz/year) |
True Mechanical Pump |
yes |
Visual Leak Indication Levels |
6 (single color) |
Sensitivity Levels |
2 |
One Touch Reset and Keypad Controls |
yes |
Mute Button |
n/a |
Battery Test |
n/a |
4 Hours / Charge |
Approx. 30 hours |
Refrigerants
CFC |
e.g. R12 |
HCFC |
e.g. R22, 502 |
HFC |
e.g. R134a, 404a, 125, 410A |
Replacements |
e.g. AZ-50, HP 62, MP 39, R1234yf, R32 |
Replacement Parts
Hard carrying case |
TIF XP-4A |
Cover for battery compartment |
TIF XP-5A |
Optional Accessories
Maintenance Kit (3 Tips with protectors) |
TIF XP-2 |